Programming 128
After selecting the proper detection scheme the Torque Detection Level (L6-02) must be specified. If the current level read by
the output current transformers rises above (overtorque) or drops below (undertorque) this level, and remains there for at least
the Torque Detection Time (L6-03), then the Torque Detection Function will change the state of any digital output configured
for Torque Detection (H2-0x = “B: Torque Detection 1 N.O.”, or “17: Torque Detection 1 N.C.”).
Fig. 92 Over Torque Detection
Fig 93 Under Torque Detection
Output
Curren
Normally
Open Torque
Detection
Digital Output
t
CLOSED
L6-03
L6-03
L6
-
02
*
*
* When the output current drops below the Torque Detection Level by
approximately 10% of the Drive’s rated output current the digital output is reset.
Closed
Open
Torque detection level -10%
TIME
Current
L6-02
Output
Current
Normally Open
Torque
Detection Digital
Output
L6-03
L6-03
L6-02
*
* When the output current rises above the Torque Detection Level by
approximately 10% of the Drive’s rated output current the digital output is reset.
*
t
t
Closed
Open
Torque detection level 10%
TIME