Yaskawa Modbus TCP/IP SI-EM3D/V Manual do Utilizador Página 48

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 47
Digital Operator Display Fault Name
EF0
Option Card External Fault
The alarm function for an external device has been triggered.
Cause Possible Solutions
An external fault was received from
the PLC and F6-03 is set to a value
other than 3.
Remove the cause of the external fault.
Remove the external fault input from the PLC.
Problem with the PLC program Check the PLC program and correct problems.
Digital Operator Display Fault Name
oFA00
Option Card Connection Error at Option Port CN5-A
The option card is incompatible with the drive.
Cause Possible Solution
Digital Operator Display Fault Name
oFA01
Option Card Fault
Option not properly connected
Cause Possible Solution
The option card connection is
faulty
Turn off the power and reconnect the option card.
Check if the option card is properly plugged into the option port. Make sure
the card is fixed properly.
Digital Operator Display Fault Name
oFA03
Option Card Fault (port A)
Option card self-diagnostic error
oFA04
Option Card Fault (port A)
An error occurred attempting to write to the option card memory.
to
oFA30 to
oFA43
Option Card Fault (port A)
Communication ID error
Cause Possible Solution
Option card or hardware is
damaged.
Replace the option card. Contact Yaskawa for consultation.
10 Troubleshooting
48
YASKAWA TOEP YAICOM 17A V1000 Option Dual-Port Modbus TCP/IP SI-EM3D/V Installation Manual
Vista de página 47