6.6 SET WORDS Instruction (SETW)
6-12
6.6 SET WORDS Instruction (SETW)
[Outline]
The SETW instruction stores the designated data (Set Data) in all registers designated by the transfer
destination register number (Dest) and the number of destination registers (Width). The storage
process is performed one word at a time in the direction in which the register number increases.
xxxxx
Transfer data Transfer destination area
V = S, I, O, M, D
Transfer
destination
register no.
xxxxx
xxxxx
xxxxx
xxxxx
…
xxxxx
xxxxx
Number of
Transfers
VWxxxxx+(n-1)
VWxxxxx+n
VWxxxxx
VWxxxxx+1
VWxxxxx+2
VWxxxxx+3
[Format]
Symbol : SETW
Full Name : Set Word
Category : MOVE
Icon :
[Parameter]
Parameter Name Setting
Dest · Any integer type register (except for # and C registers)
· Any integer type register with subscript (except for # and C registers)
Set Data · Any integer type register (except for # and C registers)
· Any integer type register with subscript (except for # and C registers)
· Constant
Width · Any integer type register
· Any integer type register with subscript
· Constant
Comentários a estes Manuais