Yaskawa Ladder Works Programming Manual Manual do Utilizador Página 134

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 220
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 133
7.5 PD CONTROL Instruction (PD)
7-13
Here, the PD operation is expressed as follows:
Y
X
= Kp + Kd×Td×S
X : deviation input value
Y : output value
The following operation is performed within the PD instruction:
Td
Y = Kp×X + Kd× ( X – X' )×
Ts
X' : previous input value
Ts : scan time set value
Input
X
Kp
Output
Y
LIMIT
DB
Z
-1
+
-
+
+
Kd
Td/Ts
[Format]
Symbol : PD
Full Name : PD Control
Category : DDC
Icon :
[Parameter]
Parameter Name Setting
Input · Any integer type and real number type register
· Any integer type and real number type register with subscript
· Subscript register
· Constant
Parameter · Register address (except for # and C registers)
· Register address with subscript (except for # and C registers)
Output · Any integer type and real number type register (except for # and C
registers)
· Any integer type and real number type register with subscript (except for #
and C registers)
· Subscript register
Vista de página 133
1 2 ... 129 130 131 132 133 134 135 136 137 138 139 ... 219 220

Comentários a estes Manuais

Sem comentários