Mon Tue Wed Thur Fri Sat Sun
0:00
1:00
2:00
3:00
4:00
5:00
6:00
Sequence Timer 3
Run at d1-03
7:00
8:00
9:00
10:00
11:00
12:00
13:00
14:00
15:00
16:00
17:00 Sequence Timer 4
18:00
19:00 Activate Sequence
20:00 Timer 4 digital output
21:00
22:00
23:00
Sequence Timer 1
Run at d1-01
Sequence Timer 2
Run at d1-02 with PI control disabled
Figure 5.51 Sequence Timer Example 1
n
Sequence Timer Example 2
Set the parameters as shown in Table 5.24 to accomplish the timer sequencing in Figure 5.52.
Table 5.24 Sequence Timer Example 2 Parameter Settings
No. Name Setting Comment
S2-01 Sequence Timer 1 Start Time 00:00
S2-02 Sequence Timer 1 Stop Time 24:00
S2-03 Sequence Timer 1 Day Selection 2 Mon to Fri
S2-04 Sequence Timer 1 Selection 1 Run
S2-05 Sequence Timer 1 Reference Source 0 Operator (d1-01)
S2-06 Sequence Timer 2 Start Time 06:00
S2-07 Sequence Timer 2 Stop Time 06:00
S2-08 Sequence Timer 2 Day Selection 3 Sat to Sun
S2-09 Sequence Timer 2 Selection 1 Run
S2-10 Sequence Timer 2 Reference Source 2 Operator (d1-03)
S2-11 Sequence Timer 3 Start Time 0:00 n/a
S2-12 Sequence Timer 3 Stop Time 0:00 n/a
S2-13 Sequence Timer 3 Day Selection 0 Timer Disabled
S2-14 Sequence Timer 3 Selection 0 n/a
S2-15 Sequence Timer 3 Reference Source 0 n/a
S2-16 Sequence Timer 4 Start Time 00:00 n/a
S2-17 Sequence Timer 4 Stop Time 00:00 n/a
S2-18 Sequence Timer 4 Day Selection 0 Timer Disabled
S2-19 Sequence Timer 4 Selection 0 n/a
S2-20 Sequence Timer 4 Reference Source 0 n/a
5.12 S: Special Parameters
190
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual