D.9 MEMOBUS/Modbus Data Table
The tables below list all MEMOBUS/Modbus data.
u
Command Data
It is possible to both read and write command data.
Note: Bits that are not used should be set to 0. Refrain from writing to reserved registers.
Register No. Contents
0000H Reserved
0001H
Operation Commands and Multi-function Inputs
bit 0 Reserved
bit 1 Reserved
bit 2 External Fault (EF0)
bit 3 Fault Reset
bit 4 Reserved
bit 5 Reserved
bit 6 Multi-Function Input 3
bit 7 Multi-Function Input 4
bit 8 Multi-Function Input 5
bit 9 Multi-Function Input 6
bit A Multi-Function Input 7
bit B to F Reserved
0002H Reserved Reserved
0003H V/f Gain
0004H, 0005H Reserved
0006H PI Target, 0.01% units, signed
0007H Analog Output Terminal FM Setting (10 V / 4000 H)
0008H Analog Output Terminal AM Setting (10 V / 4000 H)
0009H
Settings for Multi-Function Digital Outputs
bit 0 Multi-Function Contact Output 1 (terminal M1-M2)
bit 1 Multi-Function Contact Output 2 (terminal M3-M4)
bit 2 Multi-Function Contact Output 3 (terminal M5-M6)
bit 3 to 5 Reserved
bit 6 Enables the function in bit 7
bit 7 Fault Contact Output (terminal MA/MB-MC)
bit 8 to F Reserved
000AH to 000CH Reserved
000DH PI2 Setpoint
000EH Reserved
000FH
Control Selection Setting
bit 0 Reserved
bit 1 PI Setpoint Input
bit 2, bit 3 Reserved
bit 4 PI2 Target Input (enables the setting from MEMOBUS/Modbus)
bit 5 to B Reserved
bit C Enable Terminal S5 Input for Broadcast Data
bit D Enable Terminal S6 Input for Broadcast Data
bit E Enable Terminal S7 Input for Broadcast Data
bit F Reserved
0010H to 001FH Reserved
D.9 MEMOBUS/Modbus Data Table
388
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual