
u
Installation Orientation and Spacing
Install the Z1000 Bypass upright as illustrated in Figure 2.1 to maintain proper cooling.
Figure 2.1 Correct Installation Orientation
n
Single Bypass Installation
Figure 2.2 shows the installation distance required to maintain sufficient space for airflow and wiring. Install the heatsink
against a closed surface to avoid diverting cooling air around the heatsink.
B
A
Side Clearance
A
B
C
Top/Bottom Clearance
D
C
D
A – 50 mm (2.0 in.) minimum
B – 30 mm (1.2 in.) minimum
C – 120 mm (4.7 in.) minimum
D – Airflow direction
Figure 2.2 Correct Installation Spacing
2.2 Mechanical Installation
YASKAWA ELECTRIC SIEP YAIZ1B 01D YASKAWA AC Drive – Z1000 Bypass Technical Manual
41
2
Mechanical Installation
Comentários a estes Manuais